Schneider Electric Overload Relay NO/NC, 7 → 10 A, 10 A

Datasheets
Wetgeving en compliance
N.v.t.
Land van herkomst: FR
Productomschrijving

Schneider Electric | TeSys LRD Series | Thermal Overload Relays

The TeSys LRD series from Schneider Electric is a range of thermal overload relays with manual or automatic reset from 0.1 to 150 A and 0.06 to 75 kW providing greater automation control. Offering safe and effective protection LRD overload relays are reliable, covering the whole range of motor ratings up to 150A. If you are looking for an extremely compact starter they can be combined with TeSys D contactors. Designed for simple installation via screw clamp terminals, spring terminals, ring terminals or EverLink terminals, they also feature an integrated manual-automatic reset.

What is EverLink technology?
A removable terminal block, contactors and circuit-breakers can be linked without and accessory, vertically. On the same rail wiring can be connected in less than a minute. Reducing heat loss at connection points and without creep this technology provides quality wiring, continuity of service, fast assembly and reduced dimensions.

Features and Benefits:

• Pre-wiring kit
• Remote electrical, manual and automatic reset
• Terminal block for separate mounting
• Sealable flap
• Resistance to vibration & temperature cycling

Compatible contactor series:
LC1D09
LC1D12
LC1D18
LC1D25
LC1D32
LC1D38

Protection ratings & Safety features:

• TH conforming to IEC 60068
• IP20 conforming to IEC 60529
• ATEX D 94/9/CE, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508 and
CSA C22.2 No 14 standards
• ATEX INERIS, BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds register of shipping), RINA and UL certification
• Vibrations 6 Gn IEC 60068-2-6
• Shocks 15 Gn for 11 ms IEC 60068-2-7

Applications - Industry, infrastructure, building, other applications include:
• Standard motor protection
• Line protection
• Protection: motor overload, stalling, loss of phase

Specificaties
Kenmerk Waarde
FLC Motor Rating 7 → 10 A
Contact Current Rating 10 A
Pole Configuration 3P
Range TeSys
Contact Voltage Rating 690 V ac
Mounting Style Direct Contactor
Series LRD1
Normal State Configuration NO/NC
Number Of Auxiliary Contacts 2
Terminal Type Screw
Reset Method Automatic, Manual
Length 123mm
Width 45mm
Depth 66mm
Maximum Operating Temperature +60°C
Minimum Operating Temperature -20°C
Operating Temperature Range -20 → +60 °C
8 op voorraad - levertijd is 1 werkdag(en) (EU-voorraad)
168 op voorraad - levertijd is 2 werkdag(en) (UK-voorraad)
Prijs Each
Was € 56,50
51,87
(excl. BTW)
62,76
(incl. BTW)
Aantal stuks
Per stuk
1 - 9
€ 51,87
10 - 14
€ 49,77
15 +
€ 47,60
Related Products
Phase failure sensitiveTest ButtonTrip-Fault IndicationManual or automatic reset ...
Description:
Phase failure sensitiveTest ButtonTrip-Fault IndicationManual or automatic reset facilityTemp. compensated trip -20 to +55°C.
Tripping class 10 Phase failure sensitivityHand, Automatic or ...
Description:
Tripping class 10 Phase failure sensitivityHand, Automatic or manual reset selectable.
Can be used with all motors equipped with ...
Description:
Can be used with all motors equipped with PTC thermistor probes. It monitors windings temperature and ensures that the rated operating value is not exceeded, therefore guarding against faults which are often the cause of premature ageing. They can also ...
Designed to create extremely compact motor starters, the ...
Description:
Designed to create extremely compact motor starters, the LR9 series can be mounted below the LC1-D115/150 and LC1-E contactors (1, 3 or 4 pole F range contactors), Featuring built in alarm function this range of overload relays have a high ...