Fluke 1630-2 FC Earth & Ground Resistance Tester 1.5kΩ CAT III 1000 V, CAT IV 600 V

  • RS-stocknr. 134-7343
  • Fabrikantnummer FLUKE-1630-2 FC
  • Fabrikant Fluke
Datasheets
Wetgeving en compliance
N.v.t.
Land van herkomst: CN
Productomschrijving

Fluke 1630-2 FC Earth Ground LeakageTester

This 1630-2 FC offers a stakeless earth ground loop and ac leakage clamp, with Fluke Connect. Which identifies ground loop impedance without having to disconnect the ground from the grounding system, and without having to use auxiliary test stakes. Save and share data via Fluke Connect® wireless test system.

Fluke Connect® Wireless System

The 1630-2 FC supports the Fluke Connect Wireless System (may not be available in all regions). Fluke Connect wirelessly connects the clamp with an app on your smartphone or tablet. The app shows the ground resistance measurements on your smartphone or tablet display. You can save these measurements, GPS location from your phone and images to Fluke Connect Cloud storage and share with your team.

Feature and Benefits

• High-quality • Rugged
• Identify ac leakage currents without disconnecting the earth ground stake from the grounding system
• Ideal for system troubleshooting
• Heavy-duty clamp jaw stays in alignment and in calibration even in every day, on-the-job industrial environments
• The earth grounding clamp saves time by automatically recording data at pre-set intervals and saves up to 32760 measurements in memory at the set logging interval
• User-defined high/low alarm limits, for rapid measurement evaluation
• Selectable band-pass filter function removes unwanted noise from the ac leakage current measurement

Specificaties
Kenmerk Waarde
Absolute Maximum Resistance Measurement 1.5kΩ
Best Accuracy ±1.5 % of 0.02 Reading
Display Type LCD
Safety Category CAT III 1000 V, CAT IV 600 V
Battery Life 15 h
Battery Type 1.5 V AA Alkaline IEC/EN LR6
Power Source Battery
Dimensions 105 x 48 x 283mm
Weight 880g
Height 283mm
Includes Earth Ground Clamp, Hard Case, Loop Resistance Standard, Quick Reference Guide, Safety Information Guide, 4 AA Batteries
Length 105mm
Maximum Operating Temperature +50°C
Measurement Type Earth Ground Loop Resistance
Minimum Operating Temperature -10°C
Width 48mm
Model Number p 1630-2 FC
Safety Category Level CAT III, CAT IV
Safety Category Voltage 600 V, 1000 V
3 op voorraad - levertijd is 1 werkdag(en) (EU-voorraad)
18 op voorraad - levertijd is 2 werkdag(en) (UK-voorraad)
Prijs Each
1.493,00
(excl. BTW)
1.806,53
(incl. BTW)
Aantal stuks
Per stuk
1 +
€ 1.493,00
Kalibratie-opties
Related Products
A device designed to easily measure earth resistance ...
Description:
A device designed to easily measure earth resistance (in TT), monitor continuities and check installations (on standard 2P + T plugs or B.T. panels).On its dual-colour LCD screen, the Catohm NG clearly and instantly displays the correct plug connection, as ...
Electrical testers to be used on motors, generators, ...
Description:
Electrical testers to be used on motors, generators, cables, or switch gear,the tester line is designed to be safe, simple to use and gimmick-free. A perfect solution for troubleshooting, commissioning, and preventative maintenance applications. Meets IEC10101, CATIII 1000VLarge dual display ...
Kits for performing tests required by NF C ...
Description:
Kits for performing tests required by NF C 15-1001 DT-170 (differential controller)1 DT-300 (earth and continuity measuring device and extension cord)1 M-9955538 (diagnostic book 15-100)1 DT-500* (Insulation controller and connectors).
Tester for complete and rapid appraisal of earths.Multi-function ...
Description:
Tester for complete and rapid appraisal of earths.Multi-function measurement:Earth resistance, earth coupling, soil resistivity and continuity/resistance.Ergonomic:Rugged, watertight field enclosure with giant backlit LCD display.Direct access to measurements by selector switch.Battery can be recharged from mains ...