Megger LRCD220 Loop Impedance & RCD Combined Tester, Loop Impedance Test Type 2 Wire 500V

  • RS-stocknr. 711-9022
  • Fabrikantnummer LRCD220
  • Fabrikant Megger
Datasheets
Wetgeving en compliance
N.v.t.
Land van herkomst: GB
Productomschrijving

LRCD220 Loop & RCD Tester

The LRCD200 series tester combines an Earth loop impedance tester with an RCD tester. The loop tester is a non-tripping test suitable for systems protected with 30mA or larger RCDs. The RCD testing supports 10mA to 1000mA RCDs with the full range of tests. Ramp testing provides a trip current test for the testing of nuisance tripping RCDs. Suitable for use on 110V or 3 phase supplies.,Designed to meet the tough environment of site work, the instruments are rubber armoured, have a built-in protective front cover, and meet the requirements of BS7671, IEC1010 and BSEN61557. All instruments are IP54 weatherproof. The combined instrument offers all the test functions necessary for live electrical testing requirements, in a simple and cost effective instrument.

Built-in protective front cover
Tough rubber armoured case
Weatherproof to IP54
High current loop testing
Phase to phase loop testing
Auto RCD testing
1000mA RCD test
Phase rotation
110V, 230V and 415V operation
Backlit display

Note

RS is an authorised Megger distributor. Purchased though RS this product is eligible for the Megger extended 3 Year warranty

Supplied with

Durable hard carry case, instructions, 3 wire test lead with crocodile clips, BS1363 mains socket test lead, 8 off AA alkaline batteries.

Megger Loop & RCD Tester

The Megger LRCD200 series tester is a loop impedance & RCD combined 2-wire 500V tester. The loop tester is a non-tripping test suitable for systems protected with 30mA or larger RCDs. The RCD testing supports 10mA to 1000mA RCDs with the full range of tests. The tester LRCD210 with the addition of 110V loop testing and 2 wire fast testing, plus phase to phase and phase to earth measurement and automatic RCD testing with the result. The ramp testing provides a trip current test for the testing of nuisance tripping RCDs. Suitable for use on 110V or 3-phase supplies., Designed to meet the tough environment of site work, the instruments are rubber armoured, have a built-in protective front cover. The combined instrument offers all the test functions necessary for live electrical testing requirements, in a simple and cost-effective instrument.


Supplied with
Durable hard carry case, instructions, 3 wire test lead with crocodile clips, BS1363 mains socket test lead, 8 off AA alkaline batteries.

Features and Benefits


Built-in protective front cover
• Tough rubber armoured case
• High current loop testing
• Phase to phase loop testing
• Auto RCD testing
• 1000mA RCD test
• Phase rotation
• 110V, 230V and 415V operation
• Backlit display
• Extremely easy and safe to use

Certifications


IP54 rated
• IEC 61010
• Cat III 300V

Specificaties
Kenmerk Waarde
Loop Impedance Test Type 2 Wire
Calibrated RSCAL
Maximum Voltage Measurement 500V
RCD Test Type AC Selective, DC Selective
PSC Display Yes
Best Loop Test Accuracy ±2%
RCD Test Current 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA
Non-Trip Loop Test Yes
Safety Category CAT III 300 V, IEC 61010
Display Type LCD
Battery Life 2000 Tests
Battery Type AA
Power Source Battery
Dimensions 203 x 148 x 78mm
Weight 980g
Minimum Operating Temperature -5°C
Safety Category Voltage 300V
Width 148mm
Safety Category Level CAT III
Length 203mm
Model Number p LRCD220
Height 78mm
Maximum Operating Temperature +40°C
7 op voorraad - levertijd is 1 werkdag(en) plus 1 dag extra in verband met gekalibreerd artikel. Gekalibreerde producten kunnen niet worden geretourneerd.
Prijs Each
900,00
(excl. BTW)
1.089,00
(incl. BTW)
Aantal stuks
Per stuk
1 +
€ 900,00
Let op:
dit artikel is voorzien van een UK Plug.
Related Products
DET24C Additional Features. Ground resistance range : 0.050 ...
Description:
DET24C Additional Features. Ground resistance range : 0.050 Ω to 1500 ΩTrue RMS Ground leakage current range : 0.2 mA to 35 AAuto ranging & HOLD function4 digit plus 6 digit backlit LCD displayHigh and low resistance alarms256 test results ...
DET24C is a clamp-on ground resistance tester that ...
Description:
DET24C is a clamp-on ground resistance tester that set new standards in terms of access, performance, features, simplicity of operation and safety. The units are designed with flat core ends to prevent dirt build-up, ensuring measurement integrity and improved reliability ...
Single-phase measuring adapter for the PROFITEST INTRO, earthing ...
Description:
Single-phase measuring adapter for the PROFITEST INTRO, earthing contact plugs to three 4 mm safety plugs (black, blue, yellow-green), 230 V AC, touch-guarded, measuring category: CAT III, 300 V, 16 A.
Single-phase, measuring adapter for the PROFiTEST INTRO, earthing ...
Description:
Single-phase, measuring adapter for the PROFiTEST INTRO, earthing contact plugs to three 4 mm safety plugs (black, blue, yellow-green), 230 V AC, touch-guarded, measuring category: CAT III, 300 V, 16 A.