Megger LTW315-EU-BS Loop Impedance Tester 2 Wire, 3 Wire 440V ±10% CAT IV 300 V, IEC 61010 LTW315

  • RS-stocknr. 198-435
  • Fabrikantnummer LTW315-EU-BS
  • Fabrikant Megger
Datasheets
Wetgeving en compliance
N.v.t.
Land van herkomst: GB
Productomschrijving

LTW 300 Series

Earth loop impedance testers to verify the loop impedance of a live electrical circuit without the need to disconnect the electrical supply. The LTW300 series instruments offer a safe and easy 2 wire loop testing solution that does not trip 30mA RCDs and can be used on a wide range of voltages.

Backlit display
0.01Ω resolution
No-trip loop test on circuits with RCDs of ≥30 mA
3 phase circuits with RCD protection can be tested
Tests radial circuits where the circuit does not return to the origin, even where only a phase and neutral contacts are available.
10 second non trip loop test time with Auto test extension up to a further 10 seconds if noise is detected, to improve the accuracy of the test
High current loop testing for supplies that do not have an RCD fitted
AUTO START will start the loop test running as soon as the test leads are connected; no need to press the test button means much safer testing
PFC Display up to 20kA
Voltage and frequency measurement
110Vac systems including 110V centre tap to earth (55V phase to earth) can be tested on the secondary winding.
IP54 Weatherproof case
Optional 10A fused 2 wired test leads and crocodile clip set
Complies with IEC61010-1 300V CATIV safety standard and meets EN61557

Note

RS is an authorised Megger distributor. Purchased though RS this product is eligible for the Megger extended 3 Year warranty

Supplied with

Test lead set with crocodile clips, mains socket test lead, 8 AA alkaline batteries, hard carry case and instructions.

Megger Loop Impedance Tester

The Megger earth loop impedance testers are 2-wire, 440V and ±10% test loop accuracy. This tester is to verify the loop impedance of a live electrical circuit without the need to disconnect the electrical supply. The LTW300 series instruments offer a safe and easy but do not trip 30mA RCDs and can be used on a wide range of voltages. A loop test is performed with only 2 test leads. This can be either phase to earth, phase to neutral and phase to phase.

Supplied with
Test lead set with crocodile clips, mains socket test lead, 8 AA alkaline batteries, hard carry case and instructions.

Features and Benefits


Backlit display
• 0.01Ω resolution
• No-trip loop test on circuits with RCDs of ≥30 mA
• 3-phase circuits with RCD protection can be tested
• Tests radial circuits where the circuit does not return to the origin, even where only a phase and neutral contacts are available.
• 10second non-trip loop test time with autotest extension up to a further 10seconds
• if noise is detected, to improve the accuracy of the test
• High current loop testing for supplies that do not have an RCD fitted
• AUTO START will start the loop test running as soon as the test leads are connected no need to press the test button means much safer testing
• PFC display up to 20kA
• Voltage and frequency measurement
• 110Vac systems including 110V centre tap to earth (55V phase to earth) can be tested on the secondary winding.
• Optional 10A fused 2 wired test leads and crocodile clip set

Certifications


EN61557
• EN61010-1
• EN61010
• IEC61010-1 300V CATIV

Specificaties
Kenmerk Waarde
Loop Impedance Test Type 2 Wire, 3 Wire
Maximum Voltage Measurement 440V
Best Loop Test Accuracy ±10%
Non-Trip Loop Test Yes
Safety Category CAT IV 300 V, IEC 61010
Display Type LCD
Battery Type AA
Battery Life 2000 Tests
Power Source Battery
Dimensions 203 x 148 x 78mm
Weight 1kg
Height 78mm
Minimum Operating Temperature -10°C
Width 148mm
Length 203mm
Maximum Operating Temperature +50°C
Safety Category Voltage 300V
Model Number p LTW315
Safety Category Level CAT IV
13 op voorraad - levertijd is 2 werkdag(en).
Prijs Each
585,00
(excl. BTW)
707,85
(incl. BTW)
Aantal stuks
Per stuk
1 +
€ 585,00
Related Products
Offering data storage and download capabilities via a ...
Description:
Offering data storage and download capabilities via a USB port, the Fluke 1625-2 can perform 4 types of earth ground measurement. This tester is able to measure ground loop resistance using only clamps, this method doesn't require the use of ...
Introducing the RS PRO electrical tester. A brilliant ...
Description:
Introducing the RS PRO electrical tester. A brilliant tester ideal for use on motors, generators, cables, or switch-gear. This electrical tester has been designed to perform a full range of multifunctional tests, all the buttons have a positive feel a ...
Fluke 1650 series testers verify the safety of ...
Description:
Fluke 1650 series testers verify the safety of electrical installations in domestic, commercial and industrial applications.They allow electrical wiring to be certified to the new standard NF C 1500.These devices combine simplicity, efficiency, ruggedness and ergonomics to represent a new ...
The UL1430 Hook up wire is used for ...
Description:
The UL1430 Hook up wire is used for internal wiring of electronic and electrical equipment. • 100m lengths• Stranded tinned copper conductor• Various colours• 22, 24, 26, 28AWG• XLPVC Material• UL758, UL1581.