Eaton xEffect FAZ MCB Mini Circuit Breaker, 1 + N, 16 A, 10 kA, Curve C

  • RS-stocknr. 922-7099
  • Fabrikantnummer FAZ-C16/1N
  • Fabrikant Eaton
Datasheets
Wetgeving en compliance
Conform
Land van herkomst: ES
Productomschrijving

Eaton FAZ Series MCBs

Eaton FAZ- miniature circuit breakers are Current limiting design provides fast short-circuit interruption that reduces the let-through energy that can damage the circuit, Trip-free design. Breaker cannot be defeated by holding the handle in the ON position

Features and Benefits

Thermal-magnetic overcurrent protection
Power to the circuit breakers can be fed from the line or load side
Clear indication of contact position via front switch toggle
Easy installation on DIN rail. Module width of only 17.5 mm (per pole)
Six levels of short-circuit protection, categorized by B, C, D, K, S and Z curves
Small modular width of the device and accessories saves space in the panel or equipment, which can lead to cost savings
Dual rated for IEC 60947-2 standard
Module widths: 1 Pole 17.5mm, 2 pole 35mm and 3 pole 52.5mm

Standards

IEC 60947-2 Relates to Low Voltage Circuit Breakers for use in industrial and similar
Installations. In the UK traditionally known as moulded case circuit breakers
(MCCB’s) and also air circuit breakers (ACB’s).

Q: What is the differences in the Tripping Curves B, C, D and S?

A: Curve B: Tripping: 3 to 5 times the rated current.
Applications: protection of generators, persons, very long cables
Curve C: Tripping: 5 to 10 times the rated current
Applications: protection of circuits and general applications
Curve D: Tripping: 10 to 14 times the rated current
Curve S Tripping 13 to 17 times the rated current
Suitable for applications where high levels of inrush current are expected. Instantaneous trip is 13–17X rating of device (In). The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers and power supplies

Standards

IEC 898; BS/EN60-898; EN50 022/DIN46277-3 (BS5584).
FAZ-C*/* & FAZ-S*/* = IEC/EN60947-2

Specificaties
Kenmerk Waarde
Range XEffect
Series FAZ
Number of Poles 1 + N
Current Rating 16 A
Tripping Characteristics Type C
Rated AC Voltage 240 V
Rated DC Voltage 48V
Breaking Capacity 10 kA
Length 17.8mm
Width 65.5mm
Depth 80mm
Terminal Contact Type Screw
Break Time Instantaneous
Tripping Mechanism Thermal-Magnetic
Reset Actuator Type Toggle Switch
Circuit Breaker Type MCB
Special Features Current Limiting Design Provides Fast Short-Circuit Interruption, Designed for Inductive Loads, Field-Installable Shunt Trip and Auxiliary Switch Subsequent Mounting, Possibility for Sealing the Toggle In ON or OFF Position, Suitable For Branch Circuit Device Protection, Thermal-Magnetic Overcurrent Protection
Application Appliances, Business Equipment, Control Circuit, Lighting, Supplementary Protection
10 op voorraad - levertijd is 1 werkdag(en) (EU-voorraad)
14 op voorraad - levertijd is 1 werkdag(en) (UK-voorraad)
Prijs Each
45,63
(excl. BTW)
55,21
(incl. BTW)
Aantal stuks
Per stuk
1 +
€ 45,63
Related Products
ESS20 electronic circuit breaker designed to selectively protect ...
Description:
ESS20 electronic circuit breaker designed to selectively protect individual circuits powered from single switch-mode power supplies (SMPS). Easily added to a DIN/EN rail, the ESS20 provides advanced circuit protection for components used in factory automation systems. Switchable current rating ranges ...
Allen Bradley general purpose MCBs from the 1492 ...
Description:
Allen Bradley general purpose MCBs from the 1492 SP series. The MCBs have a Type D tripping characteristic and an instantaneous break time. 1, 2 or 3 pole versions available. All the MCBs incorporate screw terminals and can be DIN ...
New TeSys GV4 is a compact and robust ...
Description:
New TeSys GV4 is a compact and robust motor circuit breaker, up to 115 A with 100 kA breaking capacity, available with 3 kinds of protection: magnetic, electronic thermal magnetic, electronic thermal magnetic with advanced protections and alarming designed for ...
A range of MCB automatic cut-outs in B, ...
Description:
A range of MCB automatic cut-outs in B, C and D characteristics. To secure light, socket outlet and control current circuitsThe continuous current corresponds to the nominal current strength of fuse linksThese can be replaced by B automatic machinesThe short-circuit ...