Fluke 1777 Power Quality Analyser, 3-Phase, 2000 A Max, 1000V dc

Subtotaal (1 eenheid)*

€ 12.516,00

(excl. BTW)

€ 15.144,36

(incl. BTW)

Add to Basket
selecteer of typ hoeveelheid
Tijdelijk niet op voorraad
  • Verzending 1 stuk(s) vanaf 31 augustus 2026
Heeft u meer nodig? Klik op 'Controleer leverdata' voor extra voorraad en levertijden.
Aantal stuks
Per stuk
1 +€ 12.516,00

*prijsindicatie

RS-stocknr.:
232-0535
Artikelnummer Distrelec:
302-40-455
Fabrikantnummer:
FLUKE-1777
Fabrikant:
Fluke
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren

Merk

Fluke

Product Type

Power Quality Analyser

Maximum Current Measurement

2000A

Maximum Power Measurement

1500mW

Voltage Accuracy

±0.1 %

Number of Phases

3

Display Type

LCD

Maximum Voltage Measurement

1000V dc

Measurement Type

Voltage, Power, Current

Measurement Standards

EN

Interface Type

USB, Wireless, Bluetooth

Minimum Operating Temperature

-10°C

Power Source

Battery

Maximum Operating Temperature

50°C

Height

62mm

Standards/Approvals

IEEE 1459, IEC 61000-4-7, IEC 61000-4-15 Class F1, IEC 61000-4-30 Class A, IEC 62586 PQI-A-PI

Battery Type

Lithium-ion

Weight

2.1kg

Width

190mm

Length

280mm

Model Number

1777

Battery Life

1.5h

Maximum Frequency

69Hz

Minimum Frequency

50Hz

Land van herkomst:
RO

Fluke Power Quality Analyser, 1000V Maximum Voltage Measurement, 2000A Maximum Current Measurement - FLUKE-1777


This power quality analyser is a handheld instrument for capturing and logging electrical power and power-quality metrics in three-phase systems. It records voltage, current and power parameters automatically while offering high-frequency transient capture and onboard storage, enabling field diagnostics and subsequent computer-based analysis via supplied software.

Features & Benefits


• 1000V maximum input for broad measurement range and flexibility
• 2000A Peak current measurement to handle large conductors
• ±0.1% voltage accuracy for precise voltage assessment
• 20MHz transient sampling to reveal very fast disturbances
• Lithium-ion battery for portable use and 75min runtime
• Wireless, Bluetooth and USB interfaces for fast data transfer

**Applications**


• Suitable for energy surveys and load testing in industrial sites
• Ideal for harmonic surveys and compliance checks to standards
• Used for identifying transient-related equipment failures
• Can be used with clamps and Rogowski coils for high-current systems
• Suitable for utility power-quality surveys and power monitoring

What data storage and retrieval options are available?


Logged data is stored on internal memory or microSD and can be downloaded via USB-C, USB-A, Ethernet, WiFi, or cellular connection to analysis software.

How does the instrument assist with financial analysis of losses?


An Energy Loss Calculator mode quantifies transmission, reactive, unbalance, distortion and NEUTRAL losses and outputs monetary estimates when analysed with the included software.

Which measurement bandwidths are provided for harmonics and transients?


Harmonic measurements extend to 30kHz with supraharmonic bins

transient capture bandwidth reaches 1MHz with high sample counts for detailed waveforms.

How is time synchronisation managed for multi-site logging?


Time synchronisation is achievable using GPS or network time protocols to provide sub-millisecond to sub-second absolute UTC alignment.

What environmental and safety operating limits apply?


The unit operates between -10°C and 50°C, meets IEC measurement overvoltage categories for use at service entrances, and has IP50 ingress protection.