Siemens, 3RU2 Thermal Overload Relay 1 NO/1 NC, 1.8A, 2.5 A F.L.C, 2.5A Contact Rating, 1.5 kW 3P

Subtotaal (1 eenheid)*

€ 58,03

(excl. BTW)

€ 70,22

(incl. BTW)

Add to Basket
selecteer of typ hoeveelheid
Op voorraad
  • 19 stuk(s) klaar voor verzending vanaf een andere locatie
Heeft u meer nodig? Klik op 'Controleer leverdata' voor extra voorraad en levertijden.
Aantal stuks
Per stuk
1 +€ 58,03

*prijsindicatie

RS-stocknr.:
706-1601
Fabrikantnummer:
3RU2126-1CB0
Fabrikant:
Siemens
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren

Merk

Siemens

FLC Motor Rating

1.8, 2.5A

Product Type

Thermal Overload Relay

Relay Contact Current

2.5A

Mount Type

Direct

Series

3RU2

Power Rating

1.5kW

Pole and Throw Configuration

3P

Terminal Type

Screw

Normal State Configuration

1 NO/1 NC

Reset Method

Automatic & Manual

IP Rating

IP20

Minimum Operating Temperature

-40°C

Number of Auxiliary Contacts

2

Adjustable Current Range

1.8 → 2.5 A

Width

45mm

Length

87mm

Contact Voltage

690V ac

Maximum Operating Temperature

70°C

Standards/Approvals

IEC, EAC, WEEE (2012/19/EU), REACH, CE, UKCA, RoHS, UL, CCC

Depth

85mm

Land van herkomst:
DE

Siemens 3RU2 Series Thermal Overload Relay, 1.8 to 2.5A Adjustable Current Range, 1.5kW Power Rating - 3RU2126-1CB0


This thermal overload relay provides adjustable motor protection for three-phase circuits, detecting overloads and signalling trips for control systems. It is designed for direct mounting with screw connections and supports both manual and automatic reset modes, making it suitable for industrial control panels operating in a wide ambient temperature range.

Features & Benefits


• Adjustable current range 1.8 to 2.5A for precise motor protection
• Trip class 10 minimises nuisance trips for intermittent loads
• Rated operational voltage up to 690V for high-voltage systems
• Integrated auxiliary switch with 1 NO and 1 NC for status signalling
• Auxiliary contact currents rated to 3A at low voltages for control reliability
• IP20 front protection for safe finger-safe operation

Applications


• Suitable for protecting small three-phase motors up to 1.5 kW
• Ideal for use with contactors in industrial control panels
• Used with automation systems requiring overload feedback
• Can be used for motor starter assemblies in HVAC equipment
• Suitable for installations exposed to -40 to 70 °C ambient temperatures

How is the device connected to the main and auxiliary circuits?


Main and auxiliary circuits use screw-type terminals with top-and-bottom wiring for the main conductors and separate screws for auxiliaries.

What conductor sizes can be terminated on the main contacts?


Main contacts accept solid or stranded conductors from 1mm² up to 10 mm², including provisions for two conductors per Terminal where specified.

What electrical endurance can be expected for the auxiliary contacts?


Auxiliary contacts are rated for AC-15 switching with currents up to 3A at 24 to 125V and lower permissible currents at higher voltages, with contact rating B600/R300.

How is short-circuit protection for the auxiliary switch achieved?


Recommended protection for the auxiliary circuit uses gG fuses at 6A or fast fuses at 10A as specified for short-circuit protection.

Note

Screw Terminals can only be used with screw Terminal overloads and spring Terminals can only be used with spring Terminal overloads.

Approvals

CE, UL, CSA