Siemens 3-Pole Front Switch Disconnector -, IP65, 63A, 22 kW

Subtotaal (1 eenheid)*

€ 135,34

(excl. BTW)

€ 163,76

(incl. BTW)

Add to Basket
selecteer of typ hoeveelheid
Op voorraad
  • Plus verzending 8 stuk(s) vanaf 09 november 2026
Heeft u meer nodig? Klik op 'Controleer leverdata' voor extra voorraad en levertijden.
Aantal stuks
Per stuk
1 +€ 135,34

*prijsindicatie

RS-stocknr.:
518-7382
Fabrikantnummer:
3LD2565-0TB53
Fabrikant:
Siemens
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren

Merk

Siemens

Number of Poles

3

Product Type

Switch Disconnector

Mount Type

Front

IP Rating

IP65

Electrical Phase

3

Handle Colour

Red

Switching Current

63A

Terminal Type

Box

Series

3LD

Auxiliary Contacts Available

No

Switching Power

22kW

Minimum Operating Temperature

-25°C

Switching AC Voltage

690V ac

Padlock Compatibility

No

Maximum Operating Temperature

55°C

Depth

149mm

Hazardous Area Certification

No

Standards/Approvals

CCC, UL, VDE, CE, CSA, EAC, LRS, UKCA

Width

146mm

Land van herkomst:
DE

Siemens 3LD Series Switch Disconnector, 63A Operational Current, 22kW Switching Power - 3LD2565-0TB53


This switch disconnector is a three-pole emergency-off isolator designed for front mounting in panels and enclosures. It provides manual rotary operation with a red/yellow handle and a moulded-plastic enclosure suited for metric cable glands. The unit is intended for industrial electrical isolation where a high-power, front-access disconnect is required and is rated for ambient operation between -25°C and 55°C.

Features and Benefits:


• 63A operational current delivers secure main circuit isolation
• 22kW switching power at 400V supports high-power loads
• IP65 front protection ensures resistance to dust and water
• 690V insulation rating permits use up to medium-voltage systems
• 100000 mechanical cycles provide extended operational life

Applications


• Suitable for emergency-off requirements in industrial panels
• Ideal for isolating three-phase motor drives and starters
• Used with switchgear requiring front-mounted manual control
• Can be used for maintenance isolation on manufacturing lines
• Used for installations demanding IP65-rated external controls

What connection method does it use for the main circuit?


It employs box terminals for the main current circuit allowing single conductors up to 35mm².

Are auxiliary contacts included and can they be added?


No auxiliary contacts are fitted

up to five NO and three NC auxiliary contacts can be attached as options.

What short-circuit protection is required for the main circuit?


A gL/gG fuse rated 63A is specified for short-circuit protection in the main circuit.

How does it perform under fault current conditions?


Conditional short-circuit current with line-side gG fuse protection is rated 50kA at 690V with let-through currents up to 6kA for the switch-plus-fuse combination.

Which approvals cover its use in regulated installations?


It holds multiple approvals including UL, VDE, CE, CSA, EAC, LRS and UKCA.