GEORGIN Intrinsic Security Power Supply, 4 to 20 mA, ATEX

Subtotaal (1 doos van 1 eenheid)*

€ 344,02

(excl. BTW)

€ 416,26

(incl. BTW)

Add to Basket
selecteer of typ hoeveelheid
Op voorraad
  • 1 stuk(s) klaar voor verzending vanaf een andere locatie
Heeft u meer nodig? Klik op 'Controleer leverdata' voor extra voorraad en levertijden.
Dozen
Per Doos
1 +€ 344,02

*prijsindicatie

RS-stocknr.:
230-9448
Fabrikantnummer:
BXNT600E
Fabrikant:
GEORGIN
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren

Merk

GEORGIN

Product Type

Intrinsic Security Power Supply

Number of Channels

1

Barrier Type

Galvanic Barrier

Mount Type

DIN Rail

Hazardous Area Certification

ATEX

Terminal Type

Plug-In Cage Clamp

Safety Current Resistance

50Ω

Supply Voltage

230V ac

IP Rating

IP54

Signal Type

4 to 20 mA

Minimum Operating Temperature

-20°C

Maximum Safety Voltage

27.5V

Maximum Safety Current

80.1mA

Maximum Operating Temperature

60°C

Standards/Approvals

EN/CEI 61326, EN/CEI 61010-1, EN/CEI 60079-0, EN 60079-15, CEI 61000-6-2, EN/CEI 60079-11, EN 60079-0

Series

BXNT

Land van herkomst:
FR
The galvanically insulated interface is an associated intrinsic safety item of equipment that is installed in a safe zone or in zone 2 in an IP 54 housing, thanks to the Ex nA protection mode. Its mission is to limit the level of energy that may appear in an electric circuit routed through a potentially explosive area, whatever the connection established upstream.

In addition to its energy-limiting function, its facilitates the use of signals in safe areas (e.g., relays), converts signals (e.g., 4/20 mA to 0-10V) or duplicates signals. Other functions are also available, such as the threshold relay or powering intrinsic safety.

Transmitter power supply

Input: 1 x 4/20mA

Output: 1 x 4/20mA

Option: without, clamp terminals

Power supply: 110/230 Vac

DIN rail mounting housing

ATEX / IECEx informations:

EC type examination certificate LCIE 02 ATEX 6104X

IECEx LCI 09.0013X certificate

[Ex ia] IIC (-20 °C < Ta < 60 °C)

Group II (surface) - category (1) G/D

Installation in safe zone

Barrier for equipment installed in zone 0,1,2 et 20,21,22

See leaflet for a safe use

Gerelateerde Links

Wees als eerste op de hoogte van onze nieuwste producten en aanbiedingen

E-mailadres

De persoonlijke gegevens die u aan ons verstrekt bij het aanmelden voor deze mailinglijst worden verwerkt in overeenstemming met ons privacybeleid.