Lapp NYY-J 16 mm² 3 Core Power Cable, Black PVC, 50m

Subtotaal (1 rol van 50 meter)*

€ 1.218,27

(excl. BTW)

€ 1.474,11

(incl. BTW)

Add to Basket
selecteer of typ hoeveelheid
Tijdelijk niet op voorraad
  • Verzending vanaf 13 maart 2026
Heeft u meer nodig? Klik op 'Controleer leverdata' voor extra voorraad en levertijden.
Rol(len)
Per rol
Per meter*
1 +€ 1.218,27€ 24,365

*prijsindicatie

RS-stocknr.:
721-0709
Fabrikantnummer:
15500613
Fabrikant:
Lapp
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren

Merk

Lapp

Cross Sectional Area

16 mm²

Number of Cores

3

Sheath Colour

Black

Length

50m

Current Rating

79 A

CPR Certification

Eca

Sheath Material

PVC

Outer Diameter

20mm

Voltage Rating

1 kV, 600 V

Conductor Strand Type

Solid

Standards Met

Euroclass Eca

Fire Behaviour

Flame Retardant

Insulation Material

PVC

Core Strands

4.51 mm

Series

NYY-J

Size of Strands

4.51 mm

Maximum Operating Temperature

+50°C

Conductor Material

Bare Copper

Conductor Resistance

1.15 Ω/km

Minimum Operating Temperature

+5°C

American Wire Gauge

5 AWG

Lapp Fixed Installation Power Cable - NYY-J


From Lapp, this NYY-J cable is a widely-used power and control cable that is often found in domestic and commercial electrical wiring. As well as being used in fixed installations, the cable is designed to be used for direct burial, and burial in concrete, providing the operating temperature is adhered to.

The cable is bare copper single core with PVC with a filling compounds over the core assembly. The PVC sheath is flame retardant and robust, allowing the cable to be used in dry, damp and wet interiors. NYY-J cable is also able very resistant to UV, and so is able to be used outdoors.

Features and Benefits

• Bare copper conductors
• PVC-based outer sheath
• Suitable for outdoor use
• Flame-retardant according IEC 60332-1-2
• Above, below, flush and recess routing
• Operating temperature during installation: -5°C to +50°C
• Operating temperature in a fixed installation: -40°C to +70°C

Applications

Able to be installed in open air and underground, NYY-J cable presents a versatile power cable that should be used in where the risk of mechanical damage is unlikely. As such it can be used in brickwork and concrete, proving the concrete is not shaken, vibrated or compressed. Lapp NYY-J able is often used in;

• Power stations
• Distributor boards
• Subscriber networks